Clean air supply panel set for operating rooms with LAMINAR FLOW SUPPLY AIR PLENUM WITH LOW TURBULANCE DISPLACEMENT FLOW
The clean air supply panel set is designed for use in operating rooms that require high cleanliness and has a smooth air supply characteristic with an air velocity of approximately 0.25 M/S (LAMINAR FLOW). It is installed in areas of the operating room that require high cleanliness to prevent infection (PROTECTION CLEAN ZONE) according to the standards EN ISO 14644-1, ONORM H 6020, DIN 1946 and VDI 2083. The clean air supply panel consists of
- The housing structure is made of aluminum inside and outside through a process to prevent Corrosion with RAL 9010 baking paint
- High Efficiency Air Filter (HEPA FILTER)
- Lighting System (BACKGROUND ILLUMINATION)
- LAMINAR Air Supply Panel (LAMINARISATOR)
Technical Features
- CASING DIMENSIONS 2,506 MM x 2,506 MM x 420 MM
- PROTECTION ZONE 4.4 m2
- NUMBER OF FILTERS 4 PCS
- INITIAL FILTER PRESSURE 175 Pa
- NOMINAL VOLUME FLOW 5,180 m3/h
- AIRFLOW VELOCITY OF 0.25 M/S
Note: MARCHHART brand product, AUSTRIA, model LF-ZP 2.4 x 2.4
High-clean air conditioning system meets the criteria and standards for hospitals according to ASHRAE Application Handbook 2003. Health Care Facilities.
Clean air distribution panel set LARMINAR AIR FLO LARMINAR AIR FLOW
- Laminar flow distribution pattern (LAMINAR FLOW) (LAMINAR FLOW)
- Air speed approximately 0.25 M/S
- According to ASHRAE 2003 and the Air Conditioning Engineering Association of Thailand