Products
Operating Theatre

The operating room floor is HEAVY DUTY type rubber tile or scientific carpet in roll form with the properties of ANTISTATIC CONDUCTIVE VINYL FLOOR COVERING, brand ARMSTRONG or equivalent to EN 649 standards, approximately 2 meters wide and 2 millimeters thick. The tiles on the floor will be laid up to the walls, approximately 150 mm high. All seams will be seamlessly connected.

It is a single opening door (SINGLE HINGED DOOR) of the SEMI AIR TIGHT type with a glass window. The door size is approximately 0.90 x 2.00 meters. The top and sides of the door edge have RUBBER SEALING PROFILE rubber sheets installed and the bottom edge of the door has a DROP SEAL rubber edge installed. DROP SEAL type with equipment. The door is a hinged door that automatically closes the door, and the door handle with key is the DEAD LOCK type. Material standards – ISO 9001:2000 standard.

The secondary entrance door from the operating room to the hand washing room is designed for use in the operating room as a sliding door, brand MARKUS, model M5 or MARKRONOMIC, which is a European or American product. It has an opening size of 1,500 mm. x 2,100 mm. with a glass window size of 300 mm. x 300 mm. It is a hermetic sealing system. The top and sides of the door edge are installed with RUBBER SEALING PROFILE rubber sheets and the bottom edge of the door is installed with STRIP RIGID RUBBER SEAL rubber edges along the line with hanging rails to support the door. The sliding door runs on BALL RACES with NYLON wheels. There is a door handle made of aluminum. The door opens and closes automatically controlled by a MICRO PROCESSOR. MICRO PROCESSOR with elbow switch and NO TOUCH SWITCH. There is a SINGLE – BEAM PHOTO – ELECTRIC CELL safety system. If there is an obstacle at the door, the door will stop and open automatically in case of malfunction of the automatic open-close set or power outage. The door can be opened-closed with the door handle. The door is about 40 mm thick and can prevent noise of about 27 decibels. The door frame is made of SATIN ANODIZED EXTRUDED ALUMINIUM SATIN ANODIZED EXTRUDED ALUMINIUM. The door surface is covered with PLASTIC PLASTIC LAMINATE. The door frame and door are finished products from the same manufacturer. The main entrance door to the operating room has been tested according to the air leakage prevention standard AIR PERMEABILITY TEST SLIDING DOOR ANSI / UL 1784 or BS 476.

Note: The product is a MARKUS or KONE brand from the Netherlands.

The door for the main operating room entrance (Main Door) is designed for use in the operating room as a sliding door, brand MARKUS, model M5 or MARKRONOMIC, which is a product of Europe or America. It has an opening size of 1,500 mm. x 2,100 mm. with a 300 mm. x 300 mm. glass window, it is a hermetic sealing system, HERMETIC SEALING SLIDING DOOR. The top and sides of the door edge are installed with RUBBER SEALING PROFILE rubber sheets and the bottom edge of the door is installed with STRIP RIGID RUBBER SEAL rubber edges along the line with door hanging rails. The sliding door runs on BALL RACES with NYLON wheels. The door handle is made of aluminum. The door opens and closes automatically controlled by a MICRO PROCESSOR MICRO PROCESSOR with elbow control switches (ELBOW SWITCH) and NO TOUCH SWITCH. There is a SINGLE – BEAM PHOTO – ELECTRIC CELL safety system. If there is an obstacle at the door, the door will stop and open automatically in case of malfunction of the automatic open-close set or power outage. The door can be opened-closed with the door handle. The door is about 40 mm thick and can prevent noise of about 27 decibels. The door frame is made of SATIN ANODIZED EXTRUDED ALUMINIUM SATIN ANODIZED EXTRUDED ALUMINIUM. The door surface is covered with PLASTIC PLASTIC LAMINATE. The door frame and door are finished products from the same manufacturer. The main entrance door to the operating room has been tested according to the air leakage prevention standard AIR PERMEABILITY TEST SLIDING DOOR ANSI / UL 1784 or BS 476.

Note: The product is a MARKUS or KONE brand from the Netherlands.

Walls of operating rooms and equipment are strong and safe. Prefabricated wall plan consists of prefabricated flat panels (FLAT PANEL) with smooth surface properties, produced by the EBC TECHNOLOGY process, which has ANTIBACTERIAL properties, can prevent the growth of bacteria by not less than 99.99%, tested according to the JIS Z 2801:2 standard, does not accumulate dust and germs, prevents static electricity, ANTI STATIC, can resist acids and alkalis, easy to clean, strong and durable, suitable for use in rooms that require high cleanliness (CLEAN ROOM), 8 mm thick, TRESPA brand, TOPLAB VERTICAL model, TOPLAB VERTICAL with wall hanging rail system, assembled and installed with a galvanized steel frame by hot-dip method (HOT-DIP ZINC COST), sealed joints with anti-fungal polyurethane materials, prepare space for electrical systems, medical gases, air conditioning. The prefabricated flat panels are products that have received the following standards:

  • ANTIBACTERIAL PROPERTIES > 99.99% REDUCTION , JIS Z 2801 : 2000
  • EC-CERTIFICATE OF CONFORMITY , NEN-EN 438-7 : 2005
  • QUALITY MANAGEMENT SYSTEM ISO9001 AND ENVIROMENT MANAGEMENT SYSTEM ISO14001
  • SURFACE BURNING CHARACTERISTICS , CLASS A (TEST METHOD ASTM E84/UL 723)
    GREENGUARD IN DOOR AIR QULITY CETIFIED

Note: TRESPA products from the Netherlands.

Clean air supply panel set for operating rooms with LAMINAR FLOW SUPPLY AIR PLENUM WITH LOW TURBULANCE DISPLACEMENT FLOW
The clean air supply panel set is designed for use in operating rooms that require high cleanliness and has a smooth air supply characteristic with an air velocity of approximately 0.25 M/S (LAMINAR FLOW). It is installed in areas of the operating room that require high cleanliness to prevent infection (PROTECTION CLEAN ZONE) according to the standards EN ISO 14644-1, ONORM H 6020, DIN 1946 and VDI 2083. The clean air supply panel consists of

  • The housing structure is made of aluminum inside and outside through a process to prevent Corrosion with RAL 9010 baking paint
  • High Efficiency Air Filter (HEPA FILTER)
  • Lighting System (BACKGROUND ILLUMINATION)
  • LAMINAR Air Supply Panel (LAMINARISATOR)

Technical Features

  • CASING DIMENSIONS 2,506 MM x 2,506 MM x 420 MM
  • PROTECTION ZONE 4.4 m2
  • NUMBER OF FILTERS 4 PCS
  • INITIAL FILTER PRESSURE 175 Pa
  • NOMINAL VOLUME FLOW 5,180 m3/h
  • AIRFLOW VELOCITY OF 0.25 M/S

Note: MARCHHART brand product, AUSTRIA, model LF-ZP 2.4 x 2.4

High-clean air conditioning system meets the criteria and standards for hospitals according to ASHRAE Application Handbook 2003. Health Care Facilities.

Clean air distribution panel set LARMINAR AIR FLO LARMINAR AIR FLOW

  • Laminar flow distribution pattern (LAMINAR FLOW) (LAMINAR FLOW)
  • Air speed approximately 0.25 M/S
  • According to ASHRAE 2003 and the Air Conditioning Engineering Association of Thailand